This section details the buildings incorporated in Sinergym, separate from the other components that constitute the environment for each experiment. It also provides the default Sinergym observation and action spaces for each building, though these spaces can be customized by the user. The observation variables names would be the base name with each key at the begginning.
Important
To add new buildings to this framework, please refer to the section Adding New Buildings for Environments.
3.1. Datacenter
2ZoneDataCenterHVAC_wEconomizer.epJSON: A 491.3 m2 building divided into two asymmetrical zones (west and east zone). Each zone has an HVAC system consisting of air economizers, evaporative coolers, DX cooling coil, chilled water coil, and VAV units. The main source of heat comes from the hosted servers. The heating and cooling setpoint values are applied simultaneously to both zones.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
Heating Setpoints |
Heating_Setpoint_RL |
Schedule:Compact |
Schedule Value |
Cooling Setpoints |
Cooling_Setpoint_RL |
Schedule:Compact |
Schedule Value |
Variable |
Base Variable Name |
Keys |
---|---|---|
Site Outdoor Air Drybulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
West Zone, East Zone |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
West Zone, East Zone |
Zone Air Temperature |
air_temperature |
West Zone, East Zone |
Zone Air Relative Humidity |
air_humidity |
West Zone, East Zone |
Zone Thermal Comfort Mean Radiant Temperature |
thermal_comfort_mean_radiant_temperature |
West Zone PEOPLE, East Zone PEOPLE |
Zone Thermal Comfort Clothing Value |
thermal_comfort_clothing_value |
West Zone PEOPLE, East Zone PEOPLE |
Zone Thermal Comfort Fanger Model PPD |
thermal_comfort_fanger_model_ppd |
West Zone PEOPLE, East Zone PEOPLE |
Zone People Occupant Count |
people_occupant |
West Zone, East Zone |
People Air Temperature |
people_air_temperature |
West Zone PEOPLE, East Zone PEOPLE |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |
3.2. Small Datacenter
1ZoneDataCenterCRAC_wApproachTemp.epJSON: This file demonstrates a simple data center model with air-cooled IT equipment (ITE) served by a CRAC system. The air-cooled ITE illustrates the user of various schedules and curves to vary server power use. The CRAC system has been setup to represent a Lieber DSE 125 with pumped refrigerant economizer DX cooling coil system.Fictional 1 zone building with resistive walls. No windows. Data Center server ITE object for internal gains. No internal mass. The building is oriented due north.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
COOLING RETURN AIR SETPOINT SCHEDULE |
Cooling_Setpoint_RL |
Schedule:Compact |
Schedule Value |
SUPPLY AIR SETPOINT SCHEDULE |
Supply_Air_RL |
Schedule:Compact |
Schedule Value |
Variable |
Base Variable Name |
Key |
---|---|---|
Site Outdoor Air Drybulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
Main Zone |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
Main Zone |
Zone Air Temperature |
air_temperature |
Main Zone |
Zone Air Relative Humidity |
air_humidity |
Main Zone |
Cooling Coil Electricity Rate |
cooling_coil_demand_rate |
MAIN COOLING COIL 1 |
Fan Electricity Rate |
fan_demand_rate |
EC PLUG FAN 1 |
ITE UPS Electricity Rate |
ups_demand_rate |
DATA CENTER SERVERS |
ITE Fan Electricity Rate |
ite_fan_demand_rate |
DATA CENTER SERVERS |
ITE CPU Electricity Rate |
cpu_demand_rate |
DATA CENTER SERVERS |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |
Facility Total Building Electricity Demand Rate |
building_electricity_demand_rate |
Whole Building |
Facility Total Electricity Demand Rate |
total_electricity_demand_rate |
Whole Building |
3.3. 5Zone
5ZoneAutoDXVAV.epJSON: A single-story building divided into 5 zones (1 indoor and 4 outdoor). Its surface area is 463.6 m2, and it is equipped with a VAV package (DX cooling coil and gas heating coils) with fully auto-sized input as the HVAC system to be controlled.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
HTG-SETP-SCH |
Heating_Setpoint_RL |
Schedule:Compact |
Schedule Value |
CLG-SETP-SCH |
Cooling_Setpoint_RL |
Schedule:Compact |
Schedule Value |
Variable |
Base Variable Name |
Key |
---|---|---|
Site Outdoor Air DryBulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
SPACE5-1 |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
SPACE5-1 |
Zone Air Temperature |
air_temperature |
SPACE5-1 |
Zone Air Relative Humidity |
air_humidity |
SPACE5-1 |
Zone People Occupant Count |
people_occupant |
SPACE5-1 |
Environmental Impact Total CO2 Emissions Carbon Equivalent Mass |
co2_emission |
site |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |
Meter |
Variable Name |
---|---|
Electricity:HVAC |
total_electricity_HVAC |
3.4. Warehouse
ASHRAE9012016_Warehouse.epJSON: It is a non-residential 4598 m2 floor building, divided into 3 zones: bulk storage, fine storage and an office. The Office zone is enclosed on two sides and at the top by the Fine Storage zone, and it is the unique zone with windows. Available fuel types are gas and electricity, and it is equipped with HVAC system.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
Office Heating Schedule |
Office_Heating_RL |
Schedule:Year |
Schedule Value |
Office Cooling Schedule |
Office_Cooling_RL |
Schedule:Year |
Schedule Value |
Variable |
Base Variable Name |
Key |
---|---|---|
Site Outdoor Air DryBulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
Zone1 Office, Zone2 Fine Storage, Zone3 Bulk Storage |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
Zone1 Office, Zone2 Fine Storage |
Zone Air Temperature |
air_temperature |
Zone1 Office, Zone2 Fine Storage, Zone3 Bulk Storage |
Zone Air Relative Humidity |
air_humidity |
Zone1 Office, Zone2 Fine Storage, Zone3 Bulk Storage |
Zone People Occupant Count |
people_occupant |
Zone1 Office |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |
3.5. OfficeMedium
ASHRAE9012016_OfficeMedium.epJSON: It is a 4979.6 m2 building with 3 floors. Each floor has four perimeter zones and one core zone. Available fuel types are gas and electricity, and it is equipped with HVAC system.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
HTGSETP_SCH_YES_OPTIMUM |
Office_Heating_RL |
Schedule:Compact |
Schedule Value |
CLGSETP_SCH_YES_OPTIMUM |
Office_Cooling_RL |
Schedule:Compact |
Schedule Value |
Variable |
Base Variable Name |
Key |
---|---|---|
Site Outdoor Air DryBulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
Core_bottom |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
Core_bottom |
Zone Air Temperature |
air_temperature |
Core_bottom, Core_mid, Core_top, FirstFloor_Plenum, MidFloor_Plenum, TopFloor_Plenum, Perimeter_bot_ZN_1, Perimeter_bot_ZN_2, Perimeter_bot_ZN_3, Perimeter_bot_ZN_4, Perimeter_mid_ZN_1, Perimeter_mid_ZN_2, Perimeter_mid_ZN_3, Perimeter_mid_ZN_4, Perimeter_top_ZN_1, Perimeter_top_ZN_2, Perimeter_top_ZN_3, Perimeter_top_ZN_4 |
Zone Air Relative Humidity |
air_humidity |
Core_bottom, Core_mid, Core_top, FirstFloor_Plenum, MidFloor_Plenum, TopFloor_Plenum, Perimeter_bot_ZN_1, Perimeter_bot_ZN_2, Perimeter_bot_ZN_3, Perimeter_bot_ZN_4, Perimeter_mid_ZN_1, Perimeter_mid_ZN_2, Perimeter_mid_ZN_3, Perimeter_mid_ZN_4, Perimeter_top_ZN_1, Perimeter_top_ZN_2, Perimeter_top_ZN_3, Perimeter_top_ZN_4 |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |
3.6. ShopWithVanBattery
ShopWithVanBattery.epJSON: It is a 390.2 m2 building, with only one floor. It has five zones; four of them are perimeter zones and one in the center. This is a low-energy building with photovoltaic panel and electrical storage. It demonstrates the use of the battery model for electrical storage. It has a full HVAC model and water heating service. This is a small repair shop. Open Monday through Friday, 45 hours per week.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
HTGSETP_SCH |
Heating_Setpoint_RL |
Schedule:Compact |
Schedule Value |
CLGSETP_SCH |
Cooling_Setpoint_RL |
Schedule:Compact |
Schedule Value |
Variable |
Base Variable Name |
Key |
---|---|---|
Site Outdoor Air Drybulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
ZN_1_FLR_1_SEC_5 |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
ZN_1_FLR_1_SEC_5 |
Electric Storage Battery Charge State |
storage_battery_charge_state |
Kibam |
Electric Storage Charge Energy |
storage_charge_energy |
Kibam |
Electric Storage Charge Power |
storage_charge_power |
Kibam |
Electric Storage Discharge Energy |
storage_discharge_energy |
Kibam |
Electric Storage Discharge Power |
storage_discharge_power |
Kibam |
Electric Storage Thermal Loss Energy |
storage_thermal_loss_energy |
Kibam |
Electric Storage Thermal Loss Rate |
storage_thermal_loss_rate |
Kibam |
Zone Air Temperature |
air_temperature |
ZN_1_FLR_1_SEC_1, ZN_1_FLR_1_SEC_2, ZN_1_FLR_1_SEC_3, ZN_1_FLR_1_SEC_4, ZN_1_FLR_1_SEC_5 |
Zone Air Relative Humidity |
air_humidity |
ZN_1_FLR_1_SEC_1, ZN_1_FLR_1_SEC_2, ZN_1_FLR_1_SEC_3, ZN_1_FLR_1_SEC_4, ZN_1_FLR_1_SEC_5 |
Zone People Occupant Count |
people_count |
ZN_1_FLR_1_SEC_1, ZN_1_FLR_1_SEC_2, ZN_1_FLR_1_SEC_3, ZN_1_FLR_1_SEC_4, ZN_1_FLR_1_SEC_5 |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |
3.7. OfficeGridStorageSmoothing
OfficeGridStorageSmoothing.epJSON: It is a large office building with 12 floors and a basement, with a rectangular aspect and 46,320 m2. The building is organized in 19 zones: the basement, bot, mid and top level. Each level has a core zone and 4 perimeter zones. Floor zone is described for bot, mid and top level too. It has a battery control for charging and discharging from the grid.
The default actuators, output and meters variables are:
Actuator |
Variable Name |
Element Type |
Value Type |
---|---|---|---|
HTGSETP_SCH |
Heating_Setpoint_RL |
Schedule:Compact |
Schedule Value |
CLGSETP_SCH |
Cooling_Setpoint_RL |
Schedule:Compact |
Schedule Value |
Charge Schedule |
Charge_Rate_RL |
Schedule:Compact |
Schedule Value |
Discharge Schedule |
Discharge_Rate_RL |
Schedule:Compact |
Schedule Value |
Variable |
Base Variable Name |
Keys |
---|---|---|
Site Outdoor Air DryBulb Temperature |
outdoor_temperature |
Environment |
Site Outdoor Air Relative Humidity |
outdoor_humidity |
Environment |
Site Wind Speed |
wind_speed |
Environment |
Site Wind Direction |
wind_direction |
Environment |
Site Diffuse Solar Radiation Rate per Area |
diffuse_solar_radiation |
Environment |
Site Direct Solar Radiation Rate per Area |
direct_solar_radiation |
Environment |
Zone Thermostat Heating Setpoint Temperature |
htg_setpoint |
Basement |
Zone Thermostat Cooling Setpoint Temperature |
clg_setpoint |
Basement |
Zone Air Temperature |
air_temperature |
Multiple Keys |
Zone Air Relative Humidity |
air_humidity |
Multiple Keys |
Zone People Occupant Count |
people_count |
Multiple Keys |
Electric Storage Simple Charge State |
battery_charge_state |
Battery |
Facility Total HVAC Electricity Demand Rate |
HVAC_electricity_demand_rate |
Whole Building |